Part Details | AIR COOLER UNIT
4130-01-225-1079 A unit comprising a fin and tube heat transfer element, filters and may or may not have a motor driven fan, inclosed in a casing for the purpose of cooling and removing moisture from the air in a space where the unit is installed. It may include electric heater and/or electrostatic precipitator. Excludes units containing compressor, condenser and means for introducing air from outside sources.
Alternate Parts: H4 LVP6.0KW, H-4 LVP-6.0KW, FCU H4LVP6.0KW, FCU H4-LVP-6.0KW, 4130-01-225-1079, 01-225-1079, 4130012251079, 012251079
| Supply Group (FSG) | NSN Assigned | NIIN | Item Name Code (INC) |
|---|---|---|---|
| 41 | JAN 27, 1986 | 01-225-1079 | 11361 ( COOLER UNIT, AIR ) |
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 4130-01-225-1079
| Part Number | Cage Code | Manufacturer |
|---|---|---|
| H-4 LVP-6.0KW | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
| FCU H4-LVP-6.0KW | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
Technical Data | NSN 4130-01-225-1079
| Characteristic | Specifications |
|---|---|
| OVERALL WIDTH | 36.000 INCHES NOMINAL |
| OVERALL HEIGHT | 52.000 INCHES NOMINAL |
| OVERALL DEPTH | 14.000 INCHES NOMINAL |
| CASE MATERIAL | STEEL, GALVANIZED |
| CASE WITH BUILT-IN CONDENSATE DRAIN PAN | INCLUDED |
| NOMINAL CAPACITY IN BTU PER HOUR | 22890.0 COOLING AND 22890.0 HEATING |
| HEATER WATTAGE RATING IN KILOWATTS | 6.0 |
| TUBE MATERIAL | COPPER |
| COIL TUBE QUANTITY | 1 |
| TUBE CIRCUIT QUANTITY | 24 |
| COOLING MEDIUM | CHILLED WATER |
| CONNECTION TYPE | FLANGE UNION |
| SUPPLY CONNECTION SIZE | .625 IN. OD |
| RETURN CONNECTION SIZE | .625 IN. OD |
| FAN TYPE | F ANY ACCEPTABLE |
| FAN DRIVE TYPE | DIRECT |
| PRIME MOVER HORSEPOWER RATING | 0.500 |
| OPERATING SPEED AT RATED CAPACITY IN RPM | 1800.0 |
| SPECIAL FEATURES | MIL-A-24775; REVERSIBLE CONNECTIONS (LH/RH); HIGH IMPACT SHOCK & VIBRATION RESISTANCE; HAS LVP (LOW VOLTAGE PROTECTION) CAPABILITY |
| END ITEM IDENTIFICATION | FAN COIL UNIT |