Part Details | AIR COOLER UNIT
4130-01-225-1593 A unit comprising a fin and tube heat transfer element, filters and may or may not have a motor driven fan, inclosed in a casing for the purpose of cooling and removing moisture from the air in a space where the unit is installed. It may include electric heater and/or electrostatic precipitator. Excludes units containing compressor, condenser and means for introducing air from outside sources.
Alternate Parts: H1 LVP2.2KW, H-1 LVP-2.2KW, FCU H1LVP2.2KW, FCU H1-LVP-2.2KW, 4130-01-225-1593, 01-225-1593, 4130012251593, 012251593
| Supply Group (FSG) | NSN Assigned | NIIN | Item Name Code (INC) |
|---|---|---|---|
| 41 | JAN 29, 1986 | 01-225-1593 | 11361 ( COOLER UNIT, AIR ) |
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 4130-01-225-1593
| Part Number | Cage Code | Manufacturer |
|---|---|---|
| H-1 LVP-2.2KW | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
| FCU H1-LVP-2.2KW | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
Technical Data | NSN 4130-01-225-1593
| Characteristic | Specifications |
|---|---|
| OVERALL WIDTH | 25.000 INCHES NOMINAL |
| OVERALL HEIGHT | 50.000 INCHES NOMINAL |
| OVERALL DEPTH | 10.000 INCHES NOMINAL |
| CASE MATERIAL | STEEL, GALVANIZED |
| CASE WITH BUILT-IN CONDENSATE DRAIN PAN | INCLUDED |
| NOMINAL CAPACITY IN BTU PER HOUR | 5850.0 HEATING AND 5850.0 COOLING |
| HEATER WATTAGE RATING IN KILOWATTS | 2.2 |
| TUBE MATERIAL | COPPER |
| COIL TUBE QUANTITY | 1 |
| TUBE CIRCUIT QUANTITY | 16 |
| COOLING MEDIUM | CHILLED WATER |
| CONNECTION TYPE | FLANGE UNION |
| SUPPLY CONNECTION SIZE | .625 IN. OD |
| RETURN CONNECTION SIZE | .625 IN. OD |
| FAN TYPE | F ANY ACCEPTABLE |
| FAN DRIVE TYPE | DIRECT |
| PRIME MOVER HORSEPOWER RATING | 0.250 |
| OPERATING SPEED AT RATED CAPACITY IN RPM | 1800.0 |
| SPECIAL FEATURES | MIL-A-24775; REVERSIBLE CONNECTIONS (LH/RH); HIGH IMPACT SHOCK AND VIBRATION RESISTANCE; HAS LVP (LOW VOLTAGE PROTECTION) CAPABILITY |
| END ITEM IDENTIFICATION | FAN COIL UNIT |