Part Details | AIR COOLER UNIT
4130-01-276-1017 A unit comprising a fin and tube heat transfer element, filters and may or may not have a motor driven fan, inclosed in a casing for the purpose of cooling and removing moisture from the air in a space where the unit is installed. It may include electric heater and/or electrostatic precipitator. Excludes units containing compressor, condenser and means for introducing air from outside sources.
Alternate Parts: FCUH40.0KWLVR, FCU-H4-0.0KW-LVR, FCU H4 0.0KWLVR LH, FCU H4, 0.0KW R H LVR, 4130-01-276-1017, 01-276-1017, 4130012761017, 012761017
| Supply Group (FSG) | NSN Assigned | NIIN | Item Name Code (INC) |
|---|---|---|---|
| 41 | APR 04, 1988 | 01-276-1017 | 11361 ( COOLER UNIT, AIR ) |
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 4130-01-276-1017
| Part Number | Cage Code | Manufacturer |
|---|---|---|
| FCU-H4-0.0KW-LVR | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
| FCU H4 0.0KWLVR LH | 38450 | ENGINEERED COIL COMPANYDBA DRS MARLO COIL |
| FCU H4, 0.0KW R H LVR | D9182 | ZF INDUSTRIEANTRIEBE WITTEN GMBH |
Technical Data | NSN 4130-01-276-1017
| Characteristic | Specifications |
|---|---|
| OVERALL WIDTH | 36.000 INCHES NOMINAL |
| OVERALL HEIGHT | 14.000 INCHES NOMINAL |
| OVERALL DEPTH | 52.000 INCHES NOMINAL |
| CASE MATERIAL | STEEL, GALVANIZED |
| CASE WITH BUILT-IN CONDENSATE DRAIN PAN | INCLUDED |
| NOMINAL CAPACITY IN BTU PER HOUR | 22890.0 COOLING |
| TUBE MATERIAL | COPPER |
| COIL TUBE QUANTITY | 1 |
| TUBE CIRCUIT QUANTITY | 24 |
| COOLING MEDIUM | CHILLED WATER |
| CONNECTION TYPE | FLANGE UNION |
| SUPPLY CONNECTION SIZE | .625 IN. OD |
| RETURN CONNECTION SIZE | .625 IN. OD |
| FAN TYPE | F ANY ACCEPTABLE |
| FAN DRIVE TYPE | DIRECT |
| OPERATING SPEED AT RATED CAPACITY IN RPM | 1800.0 |
| SPECIAL FEATURES | MIL-A-24775; REVERSIBLE CONNECTIONS (RH/LH); HIGH IMPACT SHOCK & VIBRATION RESISTANCE; HAS LVR (LOW VOLTAGE RELEASE) CAPABILITY |
| END ITEM IDENTIFICATION | FAN COIL UNIT |