Part Details | DIESEL ENGINE GENERATOR SET
6115-00-621-2928 A generator set using a diesel engine as the prime mover. Excludes GENERATOR SET, DIESEL ENGINE, TRAILER MOUNTED.
Alternate Parts: ALEX 2, MILG14609, MIL-G-14609, 6115-00-621-2928, 00-621-2928, 6115006212928, 006212928
| Supply Group (FSG) | NSN Assigned | NIIN | Item Name Code (INC) |
|---|---|---|---|
| 61 | JAN 01, 1963 | 00-621-2928 | 00476 ( GENERATOR SET, DIESEL ENGINE ) |
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 6115-00-621-2928
| Part Number | Cage Code | Manufacturer |
|---|---|---|
| ALEX 2 | 75377 | KURZ & ROOT GENERATOR COMPANY, LLC |
| MIL-G-14609 | 81349 | MILITARY SPECIFICATIONSPROMULGATED BY MILITARY |
Technical Data | NSN 6115-00-621-2928
| Characteristic | Specifications |
|---|---|
| CURRENT TYPE | AC |
| AC WATTAGE RATING | 37.5 KILOWATTS AND 45.0 KILOWATTS |
| FREQUENCY RATING | 50.0 HERTZ MINIMUM AND 60.0 HERTZ MAXIMUM |
| PHASE | THREE |
| LINE TO LINE VOLTAGE IN VOLTS | B208.0$$B416.0 |
| LINE TO NEUTRAL VOLTAGE IN VOLTS | B120.0$$B240.0 |
| POWER FACTOR IN PERCENT | 80.0 |
| EXCITOR TYPE | SEPARATELY EXCITED |
| EXCITOR | INCLUDED |
| AMBIENT TEMP IN DEG CELSIUS | 49.0 |
| TEMP RISE RATING IN DEG CELSIUS FOR CONTINUOUS OPERATION | 65.0 |
| PRIME MOVER COOLING MEDIUM | LIQUID |
| COOLING METHOD | RADIATOR |
| PRIME MOVER STARTING METHOD | C ANY ACCEPTABLE |
| CRANKING VOLTAGE IN VOLTS | 24.0 |
| AUTOMATIC STARTING FEATURE | NOT PROVIDED |
| PRIME MOVER MANUFACTURER NAME | HARNISCHFEGER CORP |
| PRIME MOVER IDENTIFYING NUMBER | 387C-18 MODEL NO. |
| MOUNTING TYPE | SKID |
| OVERALL LENGTH | 84.000 INCHES NOMINAL |
| OVERALL WIDTH | 36.000 INCHES NOMINAL |
| OVERALL HEIGHT | 59.000 INCHES NOMINAL |
| RADIO INTERFERENCE SUPPRESSION | INCLUDED |
| WINTERIZATION FEATURE | INCLUDED |
| HOUSING TYPE | INCLOSED |
| INCLOSURE TYPE | FULLY INCLOSED |
| NONDEFINITIVE SPEC/STD DATA | 1 TYPE |