Part Details | STEAM TURBINE GENERATOR SET
6115-00-809-9970 A generator set using a steam turbine as the prime mover.
Alternate Parts: DLG163001967449, DLG16-300-1967449, H2400, 6115-00-809-9970, 00-809-9970, 6115008099970, 008099970
| Supply Group (FSG) | NSN Assigned | NIIN | Item Name Code (INC) |
|---|---|---|---|
| 61 | JAN 01, 1962 | 00-809-9970 | 00478 ( GENERATOR SET, STEAM TURBINE ) |
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 6115-00-809-9970
| Part Number | Cage Code | Manufacturer |
|---|---|---|
| DLG16-300-1967449 | 80064 | NAVAL SHIP SYSTEMS COMMAND |
| H2400 | 16712 | SIEMENS DEMAG DELAVALTURBOMACHINERY, INC. |
Technical Data | NSN 6115-00-809-9970
| Characteristic | Specifications |
|---|---|
| CURRENT TYPE | AC |
| AC WATTAGE RATING | 1000.0 KILOWATTS |
| FREQUENCY RATING | 60.0 HERTZ NOMINAL |
| PHASE | THREE |
| LINE TO LINE VOLTAGE IN VOLTS | 450.0 |
| POWER FACTOR IN PERCENT | 80.0 |
| EXCITOR TYPE | SELF-EXCITED |
| EXCITOR | NOT INCLUDED |
| AMBIENT TEMP IN DEG CELSIUS | 50.0 |
| MANUFACTURER NAME | ALLIS-CHALMERS |
| IDENTIFYING NUMBER | MAKG TYPE NO. |
| PRIME MOVER MANUFACTURER NAME | DELAVAL STEAM TURBINE CO |
| PRIME MOVER IDENTIFYING NUMBER | GJ-N TYPE NO. |
| STEAM OPERATING PRESSURE | 1050.0 POUNDS PER SQUARE INCH GAGE |
| STEAM TEMP RATING | 940.0 DEG FAHRENHEIT |
| TURBINE DESIGN TYPE | IMPULSE |
| EXHAUST TYPE | CONDENSING |
| STAGE TYPE | MULTIPLE |
| TURBINE TO GENERATOR COUPLING METHOD | REDUCTION GEAR |
| MOUNTING TYPE | BASE |
| OVERALL LENGTH | 153.000 INCHES NOMINAL |
| OVERALL WIDTH | 71.000 INCHES NOMINAL |
| OVERALL HEIGHT | 150.625 INCHES NOMINAL |
| ACCESSORY COMPONENT QUANTITY | A1$$A1 |
| ACCESSORY CONTROLLING AGENCY | ALLIS-CHALMERS CO; ALLIS-CHALMERS CO |
| ACCESSORY COMPONENT NAME | CONDENSER; REGULATOR,VOLTAGE |
| ACCESSORY IDENTIFYING NUMBER | 19-660-211 DRAWING NO. AND 12-500-626 DRAWING NO. |